Phoenix Contact – ESSENTIAL-PS/3AC/24DC/240W/EE – Power supply – 1018291

Primary-switched ESSENTIAL edition power supply for DIN rail mounting, input: 3-phase, output: 24 V DC / 240 W

Technical data

Input data

AC operation

Nominal input voltage range

2x / 3x 400 V AC … 500 V AC

Input voltage range

3x 320 V AC … 575 V AC

Input voltage range AC

3x 320 V AC … 575 V AC

2x 360 V AC … 575 V AC (for 2-phase operation)

Voltage type of supply voltage

AC

Inrush current

< 15 A

Inrush current integral (I2t)

0.2 A2s

AC frequency range

45 Hz … 65 Hz

Mains buffering time

> 20 ms (3x 400 V AC)

Current consumption

3x 0.6 A (400 V AC)

3x 0.5 A (480 V AC)

Nominal power consumption

284.4 VA

Protective circuit

Transient surge protection; Varistor

Power factor (cos phi)

0.59

Typical response time

< 1 s

Permissible backup fuse

B6 B10 B16

Recommended breaker for input protection

6 A … 16 A

Discharge current to PE

< 3.5 mA

Output data

Efficiency

88.5 % (at 400 V AC and nominal values)

Output characteristic

U/I

Nominal output voltage

24 V DC ±1 %

Setting range of the output voltage (USet)

22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)

Nominal output current (IN)

10 A (UOUT= 24 V DC)

Derating

55 °C … 70 °C (2.5 %/K)

Feedback voltage resistance

35 V DC

Protection against overvoltage at the output (OVP)

< 35 V DC

Max. capacitive load

unlimited

Active current limitation

approx. 15 A

Control deviation

< 1 % (change in load, static 10 % … 90 %)

< 2 % (change in load, dynamic 10 % … 90 %)

< 0.1 % (change in input voltage ±10 %)

Residual ripple

< 10 mVPP

Short-circuit-proof

yes

Output power

240 W

Peak switching voltages nominal load

< 30 mVPP

Maximum no-load power dissipation

7.5 W

Power loss nominal load max.

34 W

Rise time

< 2 ms (UOUT(10 % … 90 %))

Connection in parallel

yes, for redundancy and increased capacity

Connection in series

yes

Connection data

Input

Connection method

Screw connection

Conductor cross section, rigid min.

0.2 mm²

Conductor cross section, rigid max.

2.5 mm²

Conductor cross section flexible min.

0.2 mm²

Conductor cross section flexible max.

2.5 mm²

Conductor cross section AWG min.

24

Conductor cross section AWG max.

14

Stripping length

9 mm

Screw thread

M2,5

Tightening torque, min

0.4 Nm

Tightening torque max

0.5 Nm

Output

Connection method

Screw connection

Conductor cross section, rigid min.

0.2 mm²

Conductor cross section, rigid max.

2.5 mm²

Conductor cross section flexible min.

0.2 mm²

Conductor cross section flexible max.

2.5 mm²

Conductor cross section AWG min.

16

Conductor cross section AWG max.

12

Stripping length

9 mm

Screw thread

M2,5

Tightening torque, min

0.4 Nm

Tightening torque max

0.5 Nm

Signaling

Types of signaling

LED

Operating voltage display

Green LED

Signal output

Status display

"DC OK" LED green

Note on status display

UOUT> 21.5 V: LED lights up

Electrical properties

Number of phases

3

Insulation voltage input/output

3 kV AC (type test)

1.5 kV AC (routine test)

Insulation voltage output / PE

500 V DC

Product properties

Product type

Power supply

Product family

ESSENTIAL POWER

MTBF (IEC 61709, SN 29500)

> 700000 h

Insulation characteristics

Protection class

I (with PE connection)

Overvoltage category

III

Degree of pollution

2

Dimensions

Dimensional drawing

Width

60 mm

Height

130 mm

Depth

152.5 mm

Installation dimensions

Installation distance right/left

0 mm / 0 mm

Installation distance top/bottom

50 mm / 50 mm

Mounting

Mounting type

DIN rail mounting

With protective coating

no

Material specifications

Housing material

Metal

Environmental and real-life conditions

Ambient conditions

Degree of protection

IP20

Ambient temperature (operation)

-25 °C … 70 °C (> 55 °C Derating: 2.5 %/K)

Ambient temperature (storage/transport)

-40 °C … 85 °C

Climatic class

3K3 (in acc. with EN 60721)

Max. permissible relative humidity (operation)

≤ 95 % (at 25 °C, non-condensing)

Shock

18 ms, 30g, in each space direction (according to IEC 60068-2-27)

Vibration (operation)

< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)

15 Hz … 150 Hz, 2.3g, 90 min.

Standards and regulations

Standard – Electrical safety

EN 60950-1

Standard – Safety extra-low voltage

EN 60950-1 (SELV)

Approval – requirement of the semiconductor industry with regard to mains voltage dips

SEMI F47 – 0706 (200 V AC)

Approvals

CSA

CSA-C22.2 Nr. 107.1-01

CSA-C22.2 Nr. 60950-01

UL approvals

UL/C-UL listed UL 508

Conformity/Approvals

SIL in accordance with IEC 61508

0

Performance level according to ISO 13849

without

EMC data

Electromagnetic compatibility

Conformance with EMC Directive 2014/30/EU

Low Voltage Directive

Conformance with Low Voltage Directive 2014/35/EC

EMC requirements for noise emission

EN 61000-6-3

EN 61000-6-4

EMC requirements for noise immunity

EN 61000-6-1

EN 61000-6-2

Noise emission

Standards/regulations

EN 55011 (EN 55022) Class B

Electrostatic discharge

Standards/regulations

EN 61000-4-2

Electrostatic discharge

Contact discharge

8 kV (Test Level 4)

Discharge in air

8 kV (Test Level 3)

Comments

Criterion A

Electromagnetic HF field

Standards/regulations

EN 61000-4-3

Electromagnetic HF field

Frequency range

80 MHz … 1 GHz

Test field strength

10 V/m

Frequency range

1 GHz … 2 GHz

Test field strength

10 V/m

Frequency range

2 GHz … 3 GHz

Test field strength

10 V/m

Comments

Criterion A

Fast transients (burst)

Standards/regulations

EN 61000-4-4

Fast transients (burst)

Input

4 kV (Test Level 4 – asymmetrical)

Output

4 kV (Test Level 4 – asymmetrical)

Signal

2 kV (Test Level 3 – asymmetrical)

Comments

Criterion A

Surge voltage load (surge)

Standards/regulations

EN 61000-4-5

Surge voltage load (surge)

Input

2 kV (Test Level 3 – symmetrical)

4 kV (Test Level 4 – asymmetrical)

Output

1 kV (Test Level 2 – symmetrical)

2 kV (Test Level 3 – asymmetrical)

Comments

Criterion A

Conducted interference

Standards/regulations

EN 61000-4-6

Conducted interference

Frequency range

0.15 MHz … 80 MHz

Comments

Criterion A

Voltage

10 V (Test Level 3)

Voltage dips

Standards/regulations

EN 61000-4-11

Emitted interference

Standards/regulations

EN 61000-6-3

Radio interference voltage in acc. with EN 55011

EN 55011 (EN 55022) Class B, area of application: Industry and residential

Emitted radio interference in acc. with EN 55011

EN 55011 (EN 55022) Class B, area of application: Industry and residential

Criteria

Criterion A

Normal operating behavior within the specified limits.

Criterion B

Temporary impairment to operational behavior that is corrected by the device itself.

Commercial data

Item number

1018291

Packing unit

1 pc

Minimum order quantity

1 pc

Sales key

CMP

Product key

CMB333

GTIN

4055626502632

Weight per piece (including packing)

1,500 g

Weight per piece (excluding packing)

1,464 g

Customs tariff number

85044095

Country of origin

CN

Reviews

There are no reviews yet.

Be the first to review “Phoenix Contact – ESSENTIAL-PS/3AC/24DC/240W/EE – Power supply – 1018291”

Your email address will not be published. Required fields are marked *

Category: